Modbus register value converterModbus 寄存器数值转换

Two registers, four possible values. See all of them at once.

两个寄存器,四种可能的值。一次全看到。

Registers → value寄存器 → 数值

2 words
Separate with spaces or commas. Read as用空格或逗号分隔。按 numbers.进制解读。

Byte view字节视图

Per-register values逐寄存器读数

Value → registers数值 → 寄存器

Registers to write应写入的寄存器

—

All interpretations of these registers这组寄存器的全部解释

Each column is one byte order. Read across a row to see how much the choice changes the answer.

每一列是一种字节序。横向对比可以看出字节序对结果影响有多大。

Which byte order do I need?该用哪种字节序?

OrderAlso calledRegisters on the wireTypical sources
ABCDbig endian, Motorola, "float AB CD"A B · C DMost PLCs, Siemens, Schneider, WAGO
CDABword swapped, "mid-little"C D · A BMany energy meters, some VFDs, older Modicon
BADCbyte swapped, "mid-big"B A · D CLess common; appears in some gateways
DCBAlittle endian, IntelD C · B APC-oriented devices, some sensors

There is no standard that fixes this. The device manual is the only authority — and if the manual is silent, write a known value from the device itself (e.g. setpoint 50.0) and see which column reproduces it.

这一点没有统一标准,只能以设备手册为准。手册没写时,最可靠的办法是从设备侧写入一个已知值(比如设定温度 50.0),看哪一列能还原出它。